HSRX
HSRX Heating Cables are designed for freeze protection and process temperature maintenance of metal pipes and tanks. HSRX cables provide temperature maintenance to 300°F and withstand temperature exposure to 482°F.
HSRX is available from stock in 5,10,15,20 watts/ft, 120 volt or 208-277 volt models.
Self-regulating construction allows for maximum flexibility, cutting to length in the field, field termination, and overlap without burnout. Approved for ordinary and hazardous area use with approved Indeeco connection and termination kits.
Approvals
Specifications
Max. Intermittent Exposure Temp.
- 482°F (250°C)
Max. Maintain or Continuous Exposure Temp.
- 300°F (150°C)
Supply Voltage
- 120V or 208 – 277V
Output Wattage
- 5, 10, 15, 20W/ft @50°F (16, 33, 49, 66W/m @10°C)
Bus wire
- 16 AWG
Min. Bending Radius
- 0.8″ @70°F (20mm @20°C), 1.8″ @-76°F (45mm @-60°C)
Specifications
Min. Installation Temperature
- -76°F (-60°C)
Min. Start-up Temperature
- -40°F (-40°C)
Max. Circuit Breaker Size
- 50A
Outer Jacket Color
- Red
Heating Cable Dimensions (Nominal)
- 0.50″ x 0.20″ (13.0mm x 5.0mm)
Heating Cable Weight
- 0.0902lb/ft (0.134kg/m)