CRG
CRG® Heating Cables are designed for freeze protection of metal and plastic pipes and tanks in building and construction market applications. CRG® Cables are also designed and approved for use in roof & gutter de-icing applications. The semiconductive polymer core changes its power output versus pipe temperature to optimize power usage and prevent overheating. The cables are designed for extended service life, are third-party tested and approved to strict industry standards for building and construction market applications. Cables are available from stock for same-day shipment.
Approvals
Specifications
Max. Intermittent Exposure Temp.
- 185°F (85°C)
Max. Maintain or Continuous Exposure Temp.
- 150°F (65°C)
Supply Voltage
- 120V or 208-277V
Output Wattage
- 3, 5, 8, 10, 12* W/ft @50°F (10, 16, 26, 33, 39W/m @10°C)
(* 12W/ft only available in Supply Voltage 200 – 277V)
Bus wire
- 16 AWG
Min. Bending Radius
- 0.5″ @68°F (13mm @20°C), 1.6″ @-58°F (40mm @-50°C)
Specifications
Min. Installation Temperature
- -58°F (-50°C)
Min. Start-up Temperature
- -40°F (-40°C)
Max. Circuit Breaker Size
- 40A
Outer Jacket Color
- Dark Grey
Heating Cable Dimensions (Nominal)
- 0.49″ x 0.25″ (12.5mm x 6.0mm)
Heating Cable Weight
- 0.0741lb/ft(0.110kg/m)